Applying ISA-18.2 Alarm Criteria in Practice
Highlights
Modern control systems allow alarms to be configured on nearly any signal. Without clear governing criteria, alarms accumulate organically over time. Operators are then forced to determine which annunciations matter during abnormal situations.
ISA 18.2 addresses this issue by establishing a strict, operational definition of an alarm. This definition exists to constrain alarm usage and preserve the meaning of annunciation.
Alarm Definition per ISA-18.2
The ISA-18.2 standard[1] defines an alarm as follows:
- The condition must be abnormal
- The condition must require immediate operator action
If either requirement is not met, the indication is not an alarm. This definition is intended to be applied directly during alarm design and rationalization, not interpreted loosely or conceptually.
Immediate Operator Action as the Fundamental Criterion
An alarm must require immediate operator action to prevent an undesirable consequence. If no action is required, the condition does not qualify as an alarm. As noted by Hollifield et al. in Alarm Management: A Comprehensive Guide[2], the fundamental test of an alarm is whether it requires operator action.
Examples of conditions that do not meet this requirement include:
- Equipment operating in an expected alternate state
- Process variables trending toward limits but still within control
- Advisory notifications
- Informational or diagnostic messages
These conditions may still be operationally important, but they belong in trends, dashboards, or status displays rather than the alarm system. An alarm exists to answer one operational question:
If the correct response is no action, the annunciation is not an alarm.
Alarms are not for Engineering or Maintenance Use
They should not.
Alarms exist exclusively to demand immediate operator action. Information intended for engineering analysis, diagnostics, or maintenance planning belongs in logs, events, and monitoring systems rather than the alarm system.
For example, some control systems can integrate hardware diagnostic notifications into the control system. A smart field device may indicate elevated internal temperature. While this condition may warrant investigation, the operator is typically unable to take corrective action in real time. In such cases, the condition should be logged as an event rather than annunciated as an alarm. Periodic review of events and diagnostic logs by engineering or maintenance personnel is the appropriate mechanism for identifying components approaching failure or requiring corrective action.
Alarm systems should not be used as a substitute for maintenance or reliability monitoring processes.
Redundant Alarms
Common examples include:
- Multiple level alarms caused by a single blocked outlet
- Alarms that restate the same condition using different measurements
- Cascading alarms triggered by predictable downstream effects
In these cases, only the alarm that directs the operator to the correct first action should annunciate. Supporting information should be suppressed, delayed, or presented outside the alarm system.
Redundant alarms degrade alarm system effectiveness by obscuring priority and increasing noise during abnormal situations.
Distinguishing Alarms from Other Indications
ISA 18.2 distinguishes alarms from other types of indications.
The ISA standard defines an alert as:
ISA 18.2 defines an event as:
Alarms, alerts, and events serve different operational purposes. When these categories are not clearly separated, alarm systems accumulate non-actionable annunciation. This condition increases alarm load, reduces operator confidence, and encourages informal filtering rather than disciplined response.
A disciplined alarm philosophy explicitly defines how each type of information is used and presented.
Role of Alarm Rationalization
- Can the operator do something about the alarm?
Events in which the operator is unable to do anything to correct the process disturbance should not be an alarm - Are there consequences if the operator does not respond to the alarm in a timely manner?
If an indication is informational in nature, it should be classified as an event and not configured as an alarm. - Is there another alarm in the system that says the same thing as this alarm?
Multiple alarms should not indicate the same root cause. - Is this alarm the best indicator of the root cause of the process upset?
Alarms should be designed such that a single event does not produce multiple alarms signifying the same thing. The alarm should be configured on the best indicator of the root cause of the disturbance.
If these questions cannot be answered clearly and consistently, the alarm does not belong in the alarm system. Rationalization eliminates unnecessary and redundant alarms while preserving alarms that are truly actionable and safety relevant.
Operator Response and Alarm Discipline
Alarms as Operational Commitments
Contact our experts at Stellaro Technologies to learn how we can help apply the ISA-18.2 in your system.
References
International Society of Automation (ISA). (2016). ANSI/ISA-18.2-2016, Management of Alarm Systems for the Process Industries. [Technical Standard]. View ISA Page
Note: Requires ISA membership to view the standardHollifield, B.R., & Habibi, E. (2011). Alarm Management: A Comprehensive Guide (2nd ed.). International Society of Automation (ISA). View Book Details
Note: Requires book purchase to view book contents
