Applying ISA-18.2 Alarm Criteria in Practice

This article defines what qualifies as an alarm under ISA 18.2 and explains why strict alarm definition is essential to effective alarm management in industrial control systems.

Highlights

|
An alarm must indicate an abnormal condition that requires immediate operator action. If the operator is not expected to take action, the indication does not qualify as an alarm and should not be configured as one.
Indications that exist only to convey information or record state changes should be classified as events or alerts. Configuring informational conditions as alarms increases alarm load without improving safety or response effectiveness.
Multiple alarms triggered by the same underlying condition rarely add value. Redundant alarms compete for attention, increase cognitive load, and obscure the alarm that actually directs the correct first action.


Purpose of Alarm Definition

Alarm management effectiveness is determined primarily by how alarms are defined. Most alarm system problems originate from loose or inconsistent alarm definition rather than from technical limitations of control platforms.

Modern control systems allow alarms to be configured on nearly any signal. Without clear governing criteria, alarms accumulate organically over time. Operators are then forced to determine which annunciations matter during abnormal situations.

ISA 18.2 addresses this issue by establishing a strict, operational definition of an alarm. This definition exists to constrain alarm usage and preserve the meaning of annunciation.


Alarm Definition per ISA-18.2

The ISA-18.2 standard[1] defines an alarm as follows:

“Audible and/or visible means of indicating to the operator an equipment malfunction, process deviation, or abnormal condition requiring a timely response.” — ANSI/ISA 18.2 – Management of Alarm Systems for the Process Industries
Two requirements are mandatory:
  1. The condition must be abnormal
  2. The condition must require immediate operator action

If either requirement is not met, the indication is not an alarm. This definition is intended to be applied directly during alarm design and rationalization, not interpreted loosely or conceptually.

Immediate Operator Action as the Fundamental Criterion

An alarm must require immediate operator action to prevent an undesirable consequence. If no action is required, the condition does not qualify as an alarm. As noted by Hollifield et al. in Alarm Management: A Comprehensive Guide[2], the fundamental test of an alarm is whether it requires operator action.

Examples of conditions that do not meet this requirement include:

  • Equipment operating in an expected alternate state
  • Process variables trending toward limits but still within control
  • Advisory notifications
  • Informational or diagnostic messages

These conditions may still be operationally important, but they belong in trends, dashboards, or status displays rather than the alarm system. An alarm exists to answer one operational question:

“What must the operator do right now to prevent an undesirable consequence?”

If the correct response is no action, the annunciation is not an alarm.

Alarms are not for Engineering or Maintenance Use

A common misconception is that alarms should also exist for engineers, maintenance personnel, or system diagnostics.

They should not.

Alarms exist exclusively to demand immediate operator action. Information intended for engineering analysis, diagnostics, or maintenance planning belongs in logs, events, and monitoring systems rather than the alarm system.

For example, some control systems can integrate hardware diagnostic notifications into the control system. A smart field device may indicate elevated internal temperature. While this condition may warrant investigation, the operator is typically unable to take corrective action in real time. In such cases, the condition should be logged as an event rather than annunciated as an alarm. Periodic review of events and diagnostic logs by engineering or maintenance personnel is the appropriate mechanism for identifying components approaching failure or requiring corrective action.

Alarm systems should not be used as a substitute for maintenance or reliability monitoring processes.

Redundant Alarms

Redundant alarms are alarms that provide no new actionable information beyond what another alarm has already indicated. If an operator is already responding to a valid alarm, additional alarms caused by the same underlying condition rarely improve safety. Instead, they compete for attention and increase cognitive load.

Common examples include:

  • Multiple level alarms caused by a single blocked outlet
  • Alarms that restate the same condition using different measurements
  • Cascading alarms triggered by predictable downstream effects

In these cases, only the alarm that directs the operator to the correct first action should annunciate. Supporting information should be suppressed, delayed, or presented outside the alarm system.

Redundant alarms degrade alarm system effectiveness by obscuring priority and increasing noise during abnormal situations.

Distinguishing Alarms from Other Indications

Alarm systems are one component of the operator interface. Not all information presented to operators should be configured as alarms.

ISA 18.2 distinguishes alarms from other types of indications.

The ISA standard defines an alert as:

“Audible and/or visible means of indicating to the operator an equipment or process condition that requires awareness and which does not meet the criteria for an alarm.” — ANSI/ISA 18.2 – Management of Alarm Systems for the Process Industries

ISA 18.2 defines an event as:

“Representation of a solicited or unsolicited fact indicating a state change.” — ANSI/ISA 18.2 – Management of Alarm Systems for the Process Industries

Alarms, alerts, and events serve different operational purposes. When these categories are not clearly separated, alarm systems accumulate non-actionable annunciation. This condition increases alarm load, reduces operator confidence, and encourages informal filtering rather than disciplined response.

A disciplined alarm philosophy explicitly defines how each type of information is used and presented.

Role of Alarm Rationalization

Alarm rationalization is the formal process used to enforce alarm definition. During rationalization, each potential alarm must justify its existence by answering these questions:
  1. Can the operator do something about the alarm?
    Events in which the operator is unable to do anything to correct the process disturbance should not be an alarm

  2. Are there consequences if the operator does not respond to the alarm in a timely manner?
    If an indication is informational in nature, it should be classified as an event and not configured as an alarm.

  3. Is there another alarm in the system that says the same thing as this alarm?
    Multiple alarms should not indicate the same root cause.

  4. Is this alarm the best indicator of the root cause of the process upset?
    Alarms should be designed such that a single event does not produce multiple alarms signifying the same thing. The alarm should be configured on the best indicator of the root cause of the disturbance.

If these questions cannot be answered clearly and consistently, the alarm does not belong in the alarm system. Rationalization eliminates unnecessary and redundant alarms while preserving alarms that are truly actionable and safety relevant.

Operator Response and Alarm Discipline

Operators should be trained to respond to all alarms in the system. It is unacceptable to assume that an alarm may be ignored. If alarms are routinely ignored, whether intentionally or unintentionally, the alarm system shall be reviewed to determine whether alarms are configured correctly. The assumption that alarms may be ignored is not a justification for adding additional alarms. It is an indicator that alarm definition or rationalization has failed. In practice, it is common to see alarm systems evolve in the opposite direction. Drawing on decades of collective experience across diverse operational roles and organizations, we have frequently observed operating environments where alarms that were routinely ignored were addressed by adding additional alarms in an attempt to capture operator attention. This approach consistently increased alarm load while further reducing alarm effectiveness.

Alarms as Operational Commitments

Each alarm represents a commitment by the organization. When an alarm annunciates, it commits the operator to act and commits the system to provide clear, reliable information that supports that action. Treating alarms as conveniences rather than commitments leads to alarm systems that operators tolerate rather than trust.

Contact our experts at Stellaro Technologies to learn how we can help apply the ISA-18.2 in your system.

References

  1. International Society of Automation (ISA). (2016). ANSI/ISA-18.2-2016, Management of Alarm Systems for the Process Industries. [Technical Standard]. View ISA Page
    Note: Requires ISA membership to view the standard


  2. Hollifield, B.R., & Habibi, E. (2011). Alarm Management: A Comprehensive Guide (2nd ed.). International Society of Automation (ISA). View Book Details
    Note: Requires book purchase to view book contents